Polyhouse Optimization and Data Logging

20 SEPTEMBER 2026

On Sunday, I worked on the ventilation and data-monitoring setup of the large polyhouse at Vigyan Ashram. There are seven fans installed inside the polyhouse, which need to operate at regular intervals so that the readings from the data loggers inside the polyhouse can be compared with the readings from the external weather station and the outdoor data logger.

DISCUSSION REGARDING DATA COLLECTION

Earlier, Hemansh was working on the data collection and comparison of the polyhouse. I discussed the remaining work with him and understood the requirements of the project. He informed me that he would complete the remaining part of his project and provide the required work and data for further comparison and analysis.

DIGITAL TIMER INSTALLATION

My main task for the day was to install a digital timer for automatically controlling the seven polyhouse fans. I referred to the manufacturer’s manual and successfully installed and programmed the timer according to the required operating schedule.

The timer has been programmed to operate the fans from 7:00 AM to 7:30 PM, with a 30-minute ON/OFF interval. The fans will operate automatically throughout this period. For example, the fans will turn ON at 7:00 AM and turn OFF at 7:30 AM, then turn ON again at 8:00 AM and continue the same cycle throughout the scheduled period.

PURPOSE OF THE TIMER SETUP

The automated timer will ensure that all seven fans operate at regular intervals without requiring manual switching. This will provide consistent ventilation conditions inside the polyhouse and help in collecting comparable data from the internal data loggers, the external weather station, and the outdoor data logger.

The successful installation of the digital timer completes the automation of the fan operating schedule and will support the upcoming data collection and comparison work.

 

 

Large Polyhouse: Fan Automation, Voltage Troubleshooting and Environmental Data Monitoring

: 21–27 September 2026

1. Introduction

During the week of 21–27 September, the major focus of the large polyhouse project was testing the automated fan-control system and developing a system for analysing the environmental data generated from the polyhouse.

After installing the digital timer for automatic fan operation, an operational issue was observed in which all the fans were not starting consistently. At one point, approximately four out of the eight fans were operating while the remaining four fans were not running. This issue was investigated to identify the possible cause and to improve the reliability of the automated system.

2. Fan Automation Testing and Troubleshooting

The automated fan system was designed to operate the polyhouse fans at regular intervals. During testing, it was observed that some fans did not start automatically even though the control system was giving the ON command.

As an initial troubleshooting step, the non-running fans were manually rotated. After manually moving the fan blades, the fans started operating normally. This indicated that the problem was not simply related to the ON/OFF command from the timer and required further investigation.

The issue was discussed with Shire Sir. Based on the discussion, voltage variation was considered as one of the possible reasons for the inconsistent starting of the fans.

3. Voltage Measurement and Observation

To investigate the voltage-related issue, the supply voltage was measured using a digital meter and clamp-meter setup.

The digital timer and fan system require a supply close to the normal operating voltage of approximately 230 V. During one of the instances when a fan was not operating, the measured voltage was approximately 225 V.

The observed difference was therefore:

230 V − 225 V = 5 V

This represented a voltage reduction of approximately:

(5 ÷ 230) × 100 ≈ 2.17%

Although the measured voltage difference was relatively small, the observation suggested that supply-voltage variation could contribute to the difficulty experienced by some fans while starting. Further monitoring is required to establish whether voltage variation is consistently associated with fan-starting failures.

The troubleshooting therefore helped identify a possible electrical factor affecting the reliability of the automated fan system. Continuous observation of the supply voltage and fan operation will be useful for confirming the cause.

4. Environmental Data Monitoring

Along with testing the fan automation system, another important task was to establish a method for comparing the environmental conditions inside the large polyhouse with the outdoor conditions.

Data loggers installed inside the polyhouse provide information about the internal environmental conditions, particularly the inside temperature. The outdoor data logger provides corresponding outdoor temperature information.

In addition, the nearby weather station provides other environmental parameters such as:

  • Wind speed
  • Solar radiation
  • Outdoor temperature

By combining these datasets, it becomes possible to study the relationship between fan operation and the environmental conditions inside and outside the polyhouse.

5. Fan ON/OFF Interval and Data Correlation

The fans were programmed to operate automatically at regular intervals, with the fan status changing approximately every 30 minutes during the testing arrangement.

Because the fan status changes at a known interval, the environmental data can be compared with the corresponding fan ON and OFF periods.

The objective is to develop a dataset containing parameters such as:

  • Time / IST
  • Fan Status
  • Inside Temperature
  • Outside Temperature
  • Solar Radiation
  • Wind Speed

This combined dataset will help analyse how changes in fan operation are related to the temperature difference between the inside and outside of the polyhouse.

6. Development of the Monitoring Spreadsheet

To organise and compare the readings from different sources, a monitoring spreadsheet was developed in collaboration with Ashwini.

The spreadsheet was designed to bring together the readings from the indoor data loggers, outdoor data logger and weather station. This provides a common format for analysing the relationship between fan operation and environmental conditions.

The spreadsheet can be accessed here:


Large Polyhouse Environmental Monitoring Spreadsheet

The organised data will later be used to analyse temperature variation during fan ON and OFF periods and to understand the effect of outdoor environmental parameters such as solar radiation and wind speed.

7. Importance of Combining the Data

Monitoring only the inside temperature would not provide enough information to understand the actual performance of the fan system because outdoor weather conditions continuously change.

For example, an increase in solar radiation can increase the temperature inside the polyhouse even when the fans are operating. Similarly, higher wind speed can improve natural air movement and influence the cooling performance.

Therefore, combining inside temperature, outside temperature, solar radiation, wind speed and fan status provides a more complete picture of the polyhouse environment.

8. Work Completed During 21–27 September

  • Tested the automated operation of the large polyhouse fans.
  • Observed inconsistent starting of the fans.
  • Identified that approximately four of the eight fans were sometimes not operating.
  • Manually rotated the affected fans and observed that they subsequently started operating.
  • Discussed the issue with Shreyas  Sir.
  • Investigated supply voltage as a possible reason for the inconsistent fan starting.
  • Measured approximately 225 V during one observed non-starting condition against a nominal 230 V supply.
  • Established a system for combining indoor, outdoor and weather-station data.
  • Worked with Ashwini to develop the environmental monitoring spreadsheet.
  • Prepared the dataset structure for correlating fan status with inside temperature, outside temperature, solar radiation and wind speed.

9. Next Steps

The next stage will involve collecting sufficient data from the polyhouse and analysing the relationship between fan operation and environmental conditions.

The voltage supply will also be monitored further to determine whether voltage variation is consistently associated with fan-starting problems. If required, the electrical supply and fan-starting behaviour will be investigated in greater detail.

The environmental dataset will be used to compare fan ON and OFF periods and determine how effectively the automated ventilation system influences the internal polyhouse temperature under different outdoor conditions.

 

Polyhouse Optimization: Cooling Pad Leakage Fix, CFM Testing & Exhaust Fan Electrical Analysis

📅 Date: 26 October – 1 November 2026  |  

During the week of 26 October to 1 November, our primary work focused on optimizing the cooling system of the polyhouse. Despite having both the cooling pads and exhaust fans operating, the internal temperature of the polyhouse was still staying between 42°C and 43°C. To resolve this high-temperature issue, we systematically worked on two major problems: stopping severe water leakage from the cooling pads and diagnosing the electrical and airflow (CFM) issues of the eight exhaust fans.

1. Fixing the Cooling Pad Water Leakage

The water pump connected to the cooling pad system had a very high discharge rate and high water pressure. Because of this excessive pressure, water was spraying forcefully out of the perforated PVC distribution pipe mounted above the cooling pads and splashing directly outside, causing heavy water leakage and wastage. To reduce this wastage and regulate the water flow, we carried out three trials:

  • Trial 1 – Filling Pipe Holes with Silicone Gel: Above the cooling pads, a PVC pipe with drilled holes distributes water onto the pads. First, we tried applying silicone gel into all the holes to make the openings narrower and finer. However, this method did not work. Narrowing the holes caused a jetting effect—the speed of the water stream coming out of the holes increased even further, resulting in even more splashing and leakage outside the pad.
  • Trial 2 – Closing Alternate Holes with Tape: In our second attempt, we taped shut alternate holes along the entire PVC pipe (keeping one hole open and closing the next one in an On-Off pattern). This approach also failed because blocking half the holes increased the pressure at the remaining open holes, leading to greater water wastage.
  • Trial 3 – Installing an Inline Control Valve & Relief (Bypass) Valve (Successful Solution): Finally, we installed an additional control valve in the main supply pipeline going from the pump to the cooling pad, along with a relief (bypass) valve. With this setup, only a limited and controlled volume of water enters the overhead PVC pipe above the cooling pad, while the excess water from the high-discharge pump is diverted back through the relief return valve. This method worked perfectly and completely stopped the water leakage from the cooling pads. Along with this, we also repaired several other broken and leaking PVC pipes at the site using PVC solvent cement.

2. Exhaust Fan Troubleshooting & CFM Calculation

After fixing the cooling pad, we moved on to fixing the exhaust fans. There are a total of 8 exhaust fans installed in the polyhouse, and we observed the following issues:

  • None of the fans were running at their full rated speed. Their 4-speed regulators were only operating effectively up to speed mode 3 or 3.5.
  • Some of the fans were not starting on their own and required a manual push by hand to start rotating.
  • Fan No. 4 had suffered a short circuit and was completely damaged, so we removed it from the frame.
  • Even after removing Fan 4, two more fans (Fan No. 2 and Fan No. 3) were not running at all due to improper electrical supply.

Direct Connection (Regulator Bypass) Test

To check if the regulators were restricting the speed, we bypassed the regulators and connected the fans directly to the line. The fans ran, but their speed on a direct connection was almost identical to their speed on Mode 4 of the regulator, showing no major difference in performance.

Standalone Fan CFM Testing & Step-by-Step Calculation

To verify whether the fan unit itself (RR Kabel exhaust fan, rated at 588 CFM and 0.28 A to 0.35 A) was delivering its rated airflow, we dismantled one fan from the polyhouse and tested it separately at another location with a proper power supply. We took a round hollow duct of the same circular shape, mounted the fan at one end of the hollow duct, and switched it on. Using a vane anemometer, we measured the air velocity inside the duct, and using a measuring tape, we measured the diameter of the duct to calculate its cross-sectional area and CFM:

CFM Calculation Formula & Parameters:

1. Rated Fan CFM: 588 CFM

2. Hollow Duct Diameter (D): 30 cm = 0.30 m (Radius r = 0.15 m)

3. Cross-Sectional Area of Duct (A):

   A = π × r² = 3.1416 × (0.15 m)² = 0.07068 m²

4. Measured Air Velocity inside Duct (V): 3.7 m/s to 3.8 m/s (taken as 3.8 m/s)

5. Volumetric Air Flow Rate (Q):

   Q = Area (A) × Velocity (V) = 0.07068 m² × 3.8 m/s = 0.2686 m³/s

6. Conversion to Cubic Feet per Minute (CFM):

   Since 1 m³/s = 2118.88 CFM:

   Calculated CFM = 0.2686 × 2118.88 = 569 CFM

The calculated value of 569 CFM is almost equal to the company’s rated specification of 588 CFM. This proved that the fan itself was in good condition and capable of delivering proper airflow when operated separately outside the polyhouse.

CFM Performance Inside the Polyhouse

However, when we measured the airflow of the exact same fans while running inside the polyhouse, they failed to deliver 569 CFM. Instead, the fans inside the polyhouse were delivering drastically lower airflow:

  • One fan delivered only 424 CFM.
  • Another fan delivered 525 CFM.
  • Another fan dropped as low as 364 CFM.

3. Electrical Line Inspection: Voltage & Current Distribution Table

The drop in CFM inside the polyhouse indicated that voltage and current distribution across the fan supply lines was not proper. To investigate this thoroughly, we checked all the wiring lines connected to the fans. Using a clamp meter to measure current (Amperes) and a multimeter to measure voltage (Volts), we recorded the electrical parameters at the outside main MCB as well as at the terminals of all 8 fans inside the polyhouse. (Note: The rated current of each fan is 0.28 A to 0.35 A).

Location / Fan No. Measured Current (Amp) Measured Voltage (V) Status & Remarks
Outside (At Main MCB) 2.1 A 217 V Normal Input Voltage at MCB
Fan 1 0.1 to 0.02 A 215 V Voltage normal, but very low current
Fan 2 0.01 A 170 to 205 V Not running (Current almost zero)
Fan 3 0.01 A 195 V Not running (Current almost zero)
Fan 4 — — Removed (Short-circuited & burned out)
Fan 5 0.43 A 104 to 135 V Severe Voltage Drop (High current draw)
Fan 6 0.43 A 132 V Severe Voltage Drop (High current draw)
Fan 7 0.39 A 134 V Severe Voltage Drop
Fan 8 0.43 A 130 V Severe Voltage Drop (High current draw)

4. Diagnosis of Voltage Drop & Action Plan for Next Step

From the voltage and current table above, we identified the exact root cause of why the fans were underperforming:

  • Severe Voltage Drop Due to Water Pump Load: While the outside MCB receives 217 V and draws 2.1 A, the voltage at Fans 5, 6, 7, and 8 drops drastically to between 104 V and 135 V. This happens because the water pump used for the cooling pads runs on the same electrical supply line and consumes a large amount of power, causing a heavy voltage drop for the exhaust fans.
  • Zero Current in Fans 2 & 3: On Fans 2 and 3, voltage is present (170–205 V and 195 V), but the current flowing through them is nearly zero (0.01 A), meaning these two units are faulty and not running at all.
  • Limitation of Existing Exhaust Fans: The currently installed fans are basic exhaust fans without internal capacitors, and they are not outdoor IP-rated to handle harsh polyhouse humidity and outdoor conditions.

Planned Modifications & Next Steps:

  1. Separate Dedicated Power Line & Parallel Connection: We have decided to lay a brand-new, separate power line exclusively for the exhaust fans (isolated from the water pump). We will remove and bypass all the speed regulators and connect all the fans in a proper parallel connection so that every fan receives full, equal voltage.
  2. Replacing Damaged Fans with Outdoor IP-Rated Fans: For the fans that have burned out or stopped working, we will source new fans with a proper outdoor IP rating suitable for polyhouse conditions.
  3. Final RPM & CFM Verification: Once the separate parallel power line is installed, we expect all working fans to run at their full rated speed. We will then measure the RPM and CFM of every fan again. If the existing non-capacitor fans still fail to run at proper RPM and deliver the required CFM, we will replace them completely so the polyhouse achieves proper cooling below 42°C–43°C.

 

 

Vigyan Ashram • Polyhouse Optimization Project

 

Optimizing Polyhouse Climate Control: From Fan Failure Forensics and Statistical Audits to Heavy-Duty Staged Ventilation

Effective microclimate control inside a polyhouse relies on clean thermodynamics, balanced airflow, and dependable hardware. Over the past few weeks at Vigyan Ashram, our team conducted a thorough electrical, mechanical, and analytical audit of our large polyhouse. What started as a routine performance review evolved into a full-scale infrastructure overhaul—re-engineering our exhaust ventilation array, solving roof-level heat trapping, and establishing a clean baseline for reliable experimental data.

~4,800 ft³
Polyhouse Air Volume
5,500+ CFM
Upgraded Fan Capacity
7 Fans (5+2)
3-Stage Layout Array
30-Min Cycle
Upcoming Test Protocol

1. Initial Diagnostics: Fan Breakdowns & Voltage Troubleshooting

Our investigation began when internal cooling performance noticeably declined, even during peak midday operation when temperatures climbed to 42°C–43°C. Earlier electrical diagnostics had already flagged severe voltage drops (dipping between 104V and 135V) across the fan lines whenever the cooling pad water pump ran, starving the fans of power.

During our physical inspection and voltage checks of the existing 8-fan exhaust wall:

  • Initial Failure State: At least 4 exhaust fans were completely non-functional, leaving only 4 fans operational.
  • Direct-Line Stress Test: To isolate whether the speed regulators were causing power drops, we bypassed the regulators on the remaining 4 fans and ran them directly on mains power. Under direct load, 2 more fans failed, leaving just 2 surviving fans out of the original 8.

With 75% of the exhaust capacity offline, upgrading the ventilation system immediately became our highest operational priority.

2. Statistical Analysis & Thermodynamic Evaluation: Why Data Validation Comes After Hardware Fixes

Before replacing hardware, we reviewed the environmental dataset, statistical analysis, and thermodynamic evaluation prepared on the polyhouse. That analysis processed cleaned sensor logs—comparing internal temperature, relative humidity, and temperature drops across the structure against external weather-station parameters such as outdoor ambient temperature, solar radiation, and wind speed.

Key Conclusion from Our Review with Dixit Sir: While the statistical framework itself was sound, sitting down with Dixit Sir revealed a fundamental flaw in the underlying dataset. Because the exhaust fans were failing and underperforming throughout the logging period, active evaporative cooling was not functioning as intended. Consequently, the recorded microclimate data was skewed and inaccurate—making it impossible to reliably interpret the true thermodynamic effect of the fans, cooling pads, or outside wind speed.

Infrastructure Remediation Roadmap (Prerequisite to Clean Data)

Together with Dixit Sir, we established a clear engineering principle: fix all major physical infrastructure faults first, and then collect clean, scientifically valid datasets. Our five-point remediation roadmap includes:

  • 1. Heavy-Duty Exhaust Fan Replacement (Top Priority): Installing outdoor-capable industrial exhaust fans with sufficient airflow headroom to ensure reliable negative-pressure cooling.
  • 2. Stopping Cooling Pad Water Leakages (Completed): Sealing and repairing water leaks along the evaporative cooling pad assembly so water circulates evenly without wastage.
  • 3. Sealing Structural Air Leakages: Closing gaps and unwanted openings across the polyhouse envelope so incoming air is forced strictly through the wet cooling pads rather than bypassing them.
  • 4. Installing an Upgraded Fogger System: Deploying improved foggers inside the polyhouse for finer mist dispersion and supplementary evaporative cooling.
  • 5. Adding an External 50% Shade Net: Planning to mount a 50% shade net externally over the top of the polyhouse to cut incoming solar radiation load before heat builds up inside.

3. Root-Cause Engineering: Why the Original Fans Burned Out

Simply swapping broken fans with identical units would have guaranteed repeat failures. A closer look at the polyhouse aerodynamics and motor ratings uncovered three root causes behind the burnouts:

  • Zero Airflow Headroom (1:1 Volume-to-CFM Mismatch): Our polyhouse encloses an internal air volume of approximately 4,800 cubic feet, and the original exhaust array was rated for exactly 4,800 CFM. Because real-world systems experience static pressure drop across ducts, pads, and louvers, having zero capacity margin forced the fans to work continuously against high airflow resistance.
  • High Current Draw & Thermal Burnout (Even Without Algae Fouling): Fighting static resistance caused the fan motors to draw higher-than-rated electrical current, rapidly overheating the windings until they burned out. Crucially, this occurred even while our cooling pads were relatively clean and free of heavy algae buildup—meaning the fans failed even under minimal pad resistance. Had algae clogged the pads further, static resistance and failure rates would have been even worse.
  • Wrong Duty Class (Domestic Indoor vs. Greenhouse Environment): The original fans were built for light indoor domestic applications (such as residential kitchens or bedrooms) with clean, dry air. They were never rated for continuous outdoor/greenhouse duty involving elevated internal temperatures, constant dust, and high evaporative humidity.

4. Fan Selection & Vendor Sourcing: Balancing Capacity with Structural Constraints

Our primary selection goal was to procure heavy-duty, outdoor-resilient exhaust fans engineered to handle continuous heat, moisture, and dust. However, real-world sourcing introduced an important structural constraint:

  • The 12-Inch Cutout Constraint: All existing fan cutouts in the polyhouse frame and cladding are sized for 12-inch (300 mm) units. Specialized commercial greenhouse fans are rarely manufactured in 12-inch frames, and switching to larger diameters would have required cutting new openings in the polyethylene sheet and fabricating new structural mounts.
  • Market Availability Reality Check: We initially evaluated mid-sized commercial polyhouse fans rated at 1,500–2,000 CFM (which would have required only 3 to 4 units for the entire structure). Upon reaching out to vendors, however, those mid-capacity units were unavailable—commercial greenhouse suppliers typically stocked only large 5,000 CFM to 10,000 CFM industrial box fans.
  • Final Engineering Decision: After discussing these trade-offs with Sir, we finalized 12-inch (300 mm) heavy-duty industrial exhaust fans operating at 1,400 RPM and delivering 1,000–1,100 CFM per unit. Installing 5 new units provides ~5,500 CFM—comfortably exceeding our 4,800 CFM baseline volume and giving the motors healthy headroom against static pressure—while fitting cleanly into the existing 12-inch cutouts.

Selected Model: Polycab Superb Heavy Duty Industrial Exhaust Fan

Chosen for its rugged industrial motor build, steady high-RPM static pressure performance, and direct fit into our existing 12-inch polyhouse cutouts. Initial units installed on-site are already running smoothly under continuous greenhouse conditions.

Sweep: 300 mm (12-Inch)
Speed: 1,400 RPM
Airflow: ~1,000–1,100 CFM
Duty: Heavy-Duty Industrial
<!– Replace this div content with: Polycab Superb Heavy Duty Industrial Exhaust Fan 300mm –>
[Insert Fan Photo Here]

Polycab Superb Heavy Duty Industrial Exhaust Fan

(300 mm Sweep • 1,400 RPM)

5. Solving Thermal Stratification: Redesigned 7-Fan Layout & Staged Cooling

During our airflow review with Sir, we uncovered a critical aerodynamic flaw in how the polyhouse was cooling. Naturally buoyant hot air rises toward the roof of the structure, but our previous airflow pattern created a lower-zone short circuit: cool air entered through the wet cooling pads and exited directly through the lower fans. While the lower level stayed relatively cool, hot air remained trapped near the ceiling and continuously radiated heat back downward, driving up overall internal temperatures.

To break this thermal stratification without cutting new holes in the polyhouse, we preserved the existing 8-cutout wall matrix (3 bottom, 3 middle, 2 top) and strategically reallocated our 7 active fans (5 new + 2 surviving old fans) while sealing the single unused opening:

Wall Zone Installed Hardware Primary Aerodynamic Role
Top Row (2 Cutouts) 2 Surviving Old Exhaust Fans (with Regulator Control) Dedicated roof-level exhaust to purge rising trapped hot air before it radiates downward.
Middle Row (3 Cutouts) New Polycab Heavy-Duty Fans (300 mm, 1400 RPM) Aligned parallel to the cooling pad zone for balanced mid-canopy heat extraction.
Bottom Row (3 Cutouts) Remaining New Polycab Heavy-Duty Fans + 1 Cutout Sealed Aligned directly parallel to the wet cooling pads for maximum crop-level evaporative cooling, with the unused hole sealed tight to stop air leaks.

3-Stage Progressive Cooling Control Strategy

Rather than running all fans at full power all day, this zoned layout lets us match ventilation power precisely to outdoor heat load:

Stage 1 • Mild Heat

 

Top-Row Heat Purging

When cooling demand is low, only the 2 top fans run via regulator control—gently exhausting rising warm air from the ceiling with minimal energy consumption.

Stage 2 • Moderate Heat

 

Middle-Zone Activation

As temperatures climb, the middle-row heavy-duty fans engage alongside the top fans to pull steady cool air across the central polyhouse volume.

Stage 3 • Peak Afternoon Heat

 

Full Evaporative Cooling

During peak afternoon heat spikes, the bottom-row heavy-duty fans switch ON as well—delivering full 5,500+ CFM capacity parallel to the wet cooling pads.

6. Current Status & Upcoming Data Validation Protocol

The newly installed Polycab Superb Heavy Duty exhaust fans are performing well, and only 2 remaining fans are pending installation to complete the 7-fan array. Once the final two units are mounted and the remaining structural seals, foggers, and external 50% shade net are in place, we will begin our formal experimental validation phase.

Next Phase — 30-Minute Automated ON/OFF Comparative Trials:

Fans will be cycled on an alternating 30-minute ON / 30-minute OFF schedule while logging synchronized internal and outdoor weather-station sensors. We will specifically evaluate and compare:

• Cooling Pads ON: Exact internal temperature reduction (ΔT) relative to outdoor ambient temperature under active evaporative cooling.

• Cooling Pads OFF: Baseline temperature reduction achieved purely through forced ventilation against outdoor ambient conditions.

• Multi-Variable Statistical Validation: With reliable hardware and airtight infrastructure in place, we will finally isolate the true statistical impact of exhaust fans, cooling pads, and outdoor wind speed on polyhouse microclimate.

Re-engineering our polyhouse ventilation taught us a vital field lesson: statistical models are only as trustworthy as the physical infrastructure generating the data. By diagnosing why our domestic fans burned out, upgrading to a 5,500+ CFM heavy-duty Polycab array, and reorganizing airflow into a three-stage anti-stratification layout, we have built a rugged foundation ready for accurate microclimate validation and optimal crop growth.