Polyhouse Optimization and Data Logging
20 SEPTEMBER 2026
On Sunday, I worked on the ventilation and data-monitoring setup of the large polyhouse at Vigyan Ashram. There are seven fans installed inside the polyhouse, which need to operate at regular intervals so that the readings from the data loggers inside the polyhouse can be compared with the readings from the external weather station and the outdoor data logger.
DISCUSSION REGARDING DATA COLLECTION
Earlier, Hemansh was working on the data collection and comparison of the polyhouse. I discussed the remaining work with him and understood the requirements of the project. He informed me that he would complete the remaining part of his project and provide the required work and data for further comparison and analysis.
DIGITAL TIMER INSTALLATION
My main task for the day was to install a digital timer for automatically controlling the seven polyhouse fans. I referred to the manufacturer’s manual and successfully installed and programmed the timer according to the required operating schedule.
The timer has been programmed to operate the fans from 7:00 AM to 7:30 PM, with a 30-minute ON/OFF interval. The fans will operate automatically throughout this period. For example, the fans will turn ON at 7:00 AM and turn OFF at 7:30 AM, then turn ON again at 8:00 AM and continue the same cycle throughout the scheduled period.
PURPOSE OF THE TIMER SETUP
The automated timer will ensure that all seven fans operate at regular intervals without requiring manual switching. This will provide consistent ventilation conditions inside the polyhouse and help in collecting comparable data from the internal data loggers, the external weather station, and the outdoor data logger.
The successful installation of the digital timer completes the automation of the fan operating schedule and will support the upcoming data collection and comparison work.
Large Polyhouse: Fan Automation, Voltage Troubleshooting and Environmental Data Monitoring
: 21–27 September 2026
1. Introduction
During the week of 21–27 September, the major focus of the large polyhouse project was testing the automated fan-control system and developing a system for analysing the environmental data generated from the polyhouse.
After installing the digital timer for automatic fan operation, an operational issue was observed in which all the fans were not starting consistently. At one point, approximately four out of the eight fans were operating while the remaining four fans were not running. This issue was investigated to identify the possible cause and to improve the reliability of the automated system.
2. Fan Automation Testing and Troubleshooting
The automated fan system was designed to operate the polyhouse fans at regular intervals. During testing, it was observed that some fans did not start automatically even though the control system was giving the ON command.
As an initial troubleshooting step, the non-running fans were manually rotated. After manually moving the fan blades, the fans started operating normally. This indicated that the problem was not simply related to the ON/OFF command from the timer and required further investigation.
The issue was discussed with Shire Sir. Based on the discussion, voltage variation was considered as one of the possible reasons for the inconsistent starting of the fans.
3. Voltage Measurement and Observation
To investigate the voltage-related issue, the supply voltage was measured using a digital meter and clamp-meter setup.
The digital timer and fan system require a supply close to the normal operating voltage of approximately 230 V. During one of the instances when a fan was not operating, the measured voltage was approximately 225 V.
The observed difference was therefore:
230 V − 225 V = 5 V
This represented a voltage reduction of approximately:
(5 ÷ 230) × 100 ≈ 2.17%
Although the measured voltage difference was relatively small, the observation suggested that supply-voltage variation could contribute to the difficulty experienced by some fans while starting. Further monitoring is required to establish whether voltage variation is consistently associated with fan-starting failures.
The troubleshooting therefore helped identify a possible electrical factor affecting the reliability of the automated fan system. Continuous observation of the supply voltage and fan operation will be useful for confirming the cause.
4. Environmental Data Monitoring
Along with testing the fan automation system, another important task was to establish a method for comparing the environmental conditions inside the large polyhouse with the outdoor conditions.
Data loggers installed inside the polyhouse provide information about the internal environmental conditions, particularly the inside temperature. The outdoor data logger provides corresponding outdoor temperature information.
In addition, the nearby weather station provides other environmental parameters such as:
- Wind speed
- Solar radiation
- Outdoor temperature
By combining these datasets, it becomes possible to study the relationship between fan operation and the environmental conditions inside and outside the polyhouse.
5. Fan ON/OFF Interval and Data Correlation
The fans were programmed to operate automatically at regular intervals, with the fan status changing approximately every 30 minutes during the testing arrangement.
Because the fan status changes at a known interval, the environmental data can be compared with the corresponding fan ON and OFF periods.
The objective is to develop a dataset containing parameters such as:
- Time / IST
- Fan Status
- Inside Temperature
- Outside Temperature
- Solar Radiation
- Wind Speed
This combined dataset will help analyse how changes in fan operation are related to the temperature difference between the inside and outside of the polyhouse.
6. Development of the Monitoring Spreadsheet
To organise and compare the readings from different sources, a monitoring spreadsheet was developed in collaboration with Ashwini.
The spreadsheet was designed to bring together the readings from the indoor data loggers, outdoor data logger and weather station. This provides a common format for analysing the relationship between fan operation and environmental conditions.
The spreadsheet can be accessed here:
Large Polyhouse Environmental Monitoring Spreadsheet
The organised data will later be used to analyse temperature variation during fan ON and OFF periods and to understand the effect of outdoor environmental parameters such as solar radiation and wind speed.
7. Importance of Combining the Data
Monitoring only the inside temperature would not provide enough information to understand the actual performance of the fan system because outdoor weather conditions continuously change.
For example, an increase in solar radiation can increase the temperature inside the polyhouse even when the fans are operating. Similarly, higher wind speed can improve natural air movement and influence the cooling performance.
Therefore, combining inside temperature, outside temperature, solar radiation, wind speed and fan status provides a more complete picture of the polyhouse environment.
8. Work Completed During 21–27 September
- Tested the automated operation of the large polyhouse fans.
- Observed inconsistent starting of the fans.
- Identified that approximately four of the eight fans were sometimes not operating.
- Manually rotated the affected fans and observed that they subsequently started operating.
- Discussed the issue with Shreyas Sir.
- Investigated supply voltage as a possible reason for the inconsistent fan starting.
- Measured approximately 225 V during one observed non-starting condition against a nominal 230 V supply.
- Established a system for combining indoor, outdoor and weather-station data.
- Worked with Ashwini to develop the environmental monitoring spreadsheet.
- Prepared the dataset structure for correlating fan status with inside temperature, outside temperature, solar radiation and wind speed.
9. Next Steps
The next stage will involve collecting sufficient data from the polyhouse and analysing the relationship between fan operation and environmental conditions.
The voltage supply will also be monitored further to determine whether voltage variation is consistently associated with fan-starting problems. If required, the electrical supply and fan-starting behaviour will be investigated in greater detail.
The environmental dataset will be used to compare fan ON and OFF periods and determine how effectively the automated ventilation system influences the internal polyhouse temperature under different outdoor conditions.
Polyhouse Optimization: Cooling Pad Leakage Fix, CFM Testing & Exhaust Fan Electrical Analysis
During the week of 26 October to 1 November, our primary work focused on optimizing the cooling system of the polyhouse. Despite having both the cooling pads and exhaust fans operating, the internal temperature of the polyhouse was still staying between 42°C and 43°C. To resolve this high-temperature issue, we systematically worked on two major problems: stopping severe water leakage from the cooling pads and diagnosing the electrical and airflow (CFM) issues of the eight exhaust fans.
1. Fixing the Cooling Pad Water Leakage
The water pump connected to the cooling pad system had a very high discharge rate and high water pressure. Because of this excessive pressure, water was spraying forcefully out of the perforated PVC distribution pipe mounted above the cooling pads and splashing directly outside, causing heavy water leakage and wastage. To reduce this wastage and regulate the water flow, we carried out three trials:
- Trial 1 – Filling Pipe Holes with Silicone Gel: Above the cooling pads, a PVC pipe with drilled holes distributes water onto the pads. First, we tried applying silicone gel into all the holes to make the openings narrower and finer. However, this method did not work. Narrowing the holes caused a jetting effect—the speed of the water stream coming out of the holes increased even further, resulting in even more splashing and leakage outside the pad.
- Trial 2 – Closing Alternate Holes with Tape: In our second attempt, we taped shut alternate holes along the entire PVC pipe (keeping one hole open and closing the next one in an On-Off pattern). This approach also failed because blocking half the holes increased the pressure at the remaining open holes, leading to greater water wastage.
- Trial 3 – Installing an Inline Control Valve & Relief (Bypass) Valve (Successful Solution): Finally, we installed an additional control valve in the main supply pipeline going from the pump to the cooling pad, along with a relief (bypass) valve. With this setup, only a limited and controlled volume of water enters the overhead PVC pipe above the cooling pad, while the excess water from the high-discharge pump is diverted back through the relief return valve. This method worked perfectly and completely stopped the water leakage from the cooling pads. Along with this, we also repaired several other broken and leaking PVC pipes at the site using PVC solvent cement.
2. Exhaust Fan Troubleshooting & CFM Calculation
After fixing the cooling pad, we moved on to fixing the exhaust fans. There are a total of 8 exhaust fans installed in the polyhouse, and we observed the following issues:
- None of the fans were running at their full rated speed. Their 4-speed regulators were only operating effectively up to speed mode 3 or 3.5.
- Some of the fans were not starting on their own and required a manual push by hand to start rotating.
- Fan No. 4 had suffered a short circuit and was completely damaged, so we removed it from the frame.
- Even after removing Fan 4, two more fans (Fan No. 2 and Fan No. 3) were not running at all due to improper electrical supply.
Direct Connection (Regulator Bypass) Test
To check if the regulators were restricting the speed, we bypassed the regulators and connected the fans directly to the line. The fans ran, but their speed on a direct connection was almost identical to their speed on Mode 4 of the regulator, showing no major difference in performance.
Standalone Fan CFM Testing & Step-by-Step Calculation
To verify whether the fan unit itself (RR Kabel exhaust fan, rated at 588 CFM and 0.28 A to 0.35 A) was delivering its rated airflow, we dismantled one fan from the polyhouse and tested it separately at another location with a proper power supply. We took a round hollow duct of the same circular shape, mounted the fan at one end of the hollow duct, and switched it on. Using a vane anemometer, we measured the air velocity inside the duct, and using a measuring tape, we measured the diameter of the duct to calculate its cross-sectional area and CFM:
1. Rated Fan CFM: 588 CFM
2. Hollow Duct Diameter (D): 30 cm = 0.30 m (Radius r = 0.15 m)
3. Cross-Sectional Area of Duct (A):
A = π × r² = 3.1416 × (0.15 m)² = 0.07068 m²
4. Measured Air Velocity inside Duct (V): 3.7 m/s to 3.8 m/s (taken as 3.8 m/s)
5. Volumetric Air Flow Rate (Q):
Q = Area (A) × Velocity (V) = 0.07068 m² × 3.8 m/s = 0.2686 m³/s
6. Conversion to Cubic Feet per Minute (CFM):
Since 1 m³/s = 2118.88 CFM:
Calculated CFM = 0.2686 × 2118.88 = 569 CFM
The calculated value of 569 CFM is almost equal to the company’s rated specification of 588 CFM. This proved that the fan itself was in good condition and capable of delivering proper airflow when operated separately outside the polyhouse.
CFM Performance Inside the Polyhouse
However, when we measured the airflow of the exact same fans while running inside the polyhouse, they failed to deliver 569 CFM. Instead, the fans inside the polyhouse were delivering drastically lower airflow:
- One fan delivered only 424 CFM.
- Another fan delivered 525 CFM.
- Another fan dropped as low as 364 CFM.
3. Electrical Line Inspection: Voltage & Current Distribution Table
The drop in CFM inside the polyhouse indicated that voltage and current distribution across the fan supply lines was not proper. To investigate this thoroughly, we checked all the wiring lines connected to the fans. Using a clamp meter to measure current (Amperes) and a multimeter to measure voltage (Volts), we recorded the electrical parameters at the outside main MCB as well as at the terminals of all 8 fans inside the polyhouse. (Note: The rated current of each fan is 0.28 A to 0.35 A).
| Location / Fan No. | Measured Current (Amp) | Measured Voltage (V) | Status & Remarks |
|---|---|---|---|
| Outside (At Main MCB) | 2.1 A | 217 V | Normal Input Voltage at MCB |
| Fan 1 | 0.1 to 0.02 A | 215 V | Voltage normal, but very low current |
| Fan 2 | 0.01 A | 170 to 205 V | Not running (Current almost zero) |
| Fan 3 | 0.01 A | 195 V | Not running (Current almost zero) |
| Fan 4 | — | — | Removed (Short-circuited & burned out) |
| Fan 5 | 0.43 A | 104 to 135 V | Severe Voltage Drop (High current draw) |
| Fan 6 | 0.43 A | 132 V | Severe Voltage Drop (High current draw) |
| Fan 7 | 0.39 A | 134 V | Severe Voltage Drop |
| Fan 8 | 0.43 A | 130 V | Severe Voltage Drop (High current draw) |
4. Diagnosis of Voltage Drop & Action Plan for Next Step
From the voltage and current table above, we identified the exact root cause of why the fans were underperforming:
- Severe Voltage Drop Due to Water Pump Load: While the outside MCB receives 217 V and draws 2.1 A, the voltage at Fans 5, 6, 7, and 8 drops drastically to between 104 V and 135 V. This happens because the water pump used for the cooling pads runs on the same electrical supply line and consumes a large amount of power, causing a heavy voltage drop for the exhaust fans.
- Zero Current in Fans 2 & 3: On Fans 2 and 3, voltage is present (170–205 V and 195 V), but the current flowing through them is nearly zero (0.01 A), meaning these two units are faulty and not running at all.
- Limitation of Existing Exhaust Fans: The currently installed fans are basic exhaust fans without internal capacitors, and they are not outdoor IP-rated to handle harsh polyhouse humidity and outdoor conditions.
Planned Modifications & Next Steps:
- Separate Dedicated Power Line & Parallel Connection: We have decided to lay a brand-new, separate power line exclusively for the exhaust fans (isolated from the water pump). We will remove and bypass all the speed regulators and connect all the fans in a proper parallel connection so that every fan receives full, equal voltage.
- Replacing Damaged Fans with Outdoor IP-Rated Fans: For the fans that have burned out or stopped working, we will source new fans with a proper outdoor IP rating suitable for polyhouse conditions.
- Final RPM & CFM Verification: Once the separate parallel power line is installed, we expect all working fans to run at their full rated speed. We will then measure the RPM and CFM of every fan again. If the existing non-capacitor fans still fail to run at proper RPM and deliver the required CFM, we will replace them completely so the polyhouse achieves proper cooling below 42°C–43°C.