Blackwater is water that has been mixed with waste from the toilet. Because of the potential for contamination by pathogens and grease, water from kitchens and dishwashers should be excluded from grey water and considered as blackwater. Each wastewater type must be treated differently and can be used in various ways. Blackwater requires biological or chemical treatment and disinfection before reuse.
Objective :
- To check the effect of bio-beds for treatment of black water.
- To compare the three systems used for treatment –
- Flood and drain system
- System with bubbler
- system without bubbler
06/04/2022 – 07/04/2022
Collection of blackwater and selection of plants
Determination of COD (Chemical Oxygen Demand)
Reagents –
- Potassium dichromate (K2Cr2O7).
- Mercuric sulphate (HgSO4)
- Sulfuric acid (H2SO4)
- Ferrous ammonium sulphate (FAS)
- Ferron indicator
- Potassium hydrogen phosphate (KHP)
- 250 ml Erlenmeyer flask
- Reflux condenser
- COD tubes
- Measuring cylinder
- Analytical balance
- COD tube stands
Procedure –
- Take 0.4 gm. HgSo4 (mercuric sulphate) in COD tubes.
- Add 20 ml sample in each COD tube (20 ml water sample, 20 ml KHP solution).
- Add 20 ml distilled water in each COD tube.
- Add stones (crush on beads) 1 or 2 pieces.
- Add 10 ml (0.25 N) K2Cr2O7 Potassium dichromate solutions.
- Add 30 ml conc sulfuric acid slowly along with swirling.
- If the solution turns green add more known quantities of K2Cr2O7 solution.
- Kept COD tubes in COD apparatus to digest the sample.
- Attach condenser & set 150 Degree Celsius temperature.
- Kept for 2 hours filled COD tubes in COD apparatus for 150 degree Celsius.
- After 2 hours switch off & remove COD tubes & cooled sample for room temperature.
- Take the above sample in a conical flask. Add 150 ml distilled water.
- Titration: – Titrate above solution with 0.1 N FAS (ferrous ammonium sulphate) solution by using Ferron indicator (add 3-4 drops). The end point of this titration is blue green to reddish brown.
Formula of COD
COD = {(a-b) X N X 8000}/ml of sample solution
Where,
- A-Reading blank solution.
- B-Reading with sample solutions
- N- Normality of FAS solution
Dilution factor = ( ml of sample + distilled water )/ ml of sample
Calculation of COD
Sample | Readings | COD (mg/lit) |
Blank | 10.4 | – |
KPH | 4.6 | 529 |
Black water | 8.1 | 2340 |
Grey water | 8.9 | 612 |
Sample | Readings | COD (mg/lit) |
Blank | 10.1 | – |
Tap water | 9.5 | 61.2 |
Blackwater | 8.5 | 1632 |
Greywater | 9.4 | 714 |
06/04/2022-10/04/2022
Collection of material
The material required for setup of systems for treatment of black water is as follows:
- Buckets
- Bubbler
- Stand
- Lateral
- T-joint
- Elbow
- Grommet
- wires
- Timer
- Sub-mersible pump 18 watt
- ARDUINO
11/04/2022-25/04/2022
Bill of material
The set-up of two systems i.e. bubbling and without bubbling is done.
- Bubbling system : In bubbling system, two buckets are used in which 17 litres of black water is filled. In first bucket, water hyacinth is planted and in second indian shot is planted. bubblers are used for aeration.
- Without bubbling system: This system is same as bubbling system. Only difference is bubblers are not used.
Flood and drain system: In this system, two buckets and two reservoirs are used. Buckets are to be placed on stand and reservoir will be under the stand.The bucket in which Indian shot is to be planted is connected with drip pipe at bottom. Hence, the black water will drain out from bottom. And the bucket in which water hyacinth is to be planted is connected with drip pipe at a height of 5 cm from side. This drip pipes are connected with submersible pumps. A timer is to be used for this system. Both pumps will operate on 1 timer.
3D CAD Designing of blackwater system
19/04/2022 – 24/04/2022
ARDUINO set-up of blackwater system:
Block diagram:
ARDUINO CODE of blackwater system :
25/04/2022
Determined COD
without bubbler | with bubbler | flood and drain | |
Initial COD (day 1) (mg/lit) | 2340 | 2340 | 2340 |
Initial COD (day 1) (mg/lit) | 1632 | 1632 | 1632 |
After 17 days (mg/lit) | 1830 | 2142 | 1326 |
COD is decreased in every system. But maximum decrease in COD is found in flood and drain system compared to others.
30/04/2022
Re-setup of black water system
The three systems of black water were setup on different times and the results cannot be compared effectively. So, the systems are set again at same time. For this, the black water in previous systems is mixed and used.
29/04/2022
Determined COD:
Without bubbler | With bubbler | Flood and drain | |
Initial COD (mg/lit) | 918 | 918 | 918 |
29/04/2022 – 03/05/2022
Determined COD
Without bubbler (Water hyacinth) | Without bubbler (Indian shot) | With bubbler (Water hyacinth) | With bubbler (Indian shot) | Flood and drain (Water hyacinth) | Flood and drain (Indian shot) | |
Initial COD (mg/lit) 30/04/2022 | 918 | 918 | 918 | 918 | 918 | 918 |
03/05/2022 | 714 | 714 | 714 | 510 | 510 | 306 |
Percentage losses in COD
Without bubbler (Water hyacinth) | Without bubbler (Indian shot) | With bubbler (Water hyacinth) | With bubbler (Indian shot) | Flood and drain (Water hyacinth) | Flood and drain (Indian shot) | |
03/05/2022 | 22.2% | 22.2% | 22.2% | 44.4% | 44.4% | 66.6% |
06/05/2022 | 33.3% | 44.4% | 44.4% | 55.5% | 66.6% | 77.7% |
From above table, it is seen that flood and drain system with Indian shot gives highest decrease in COD comparing with all systems.
10/05/2022
Trial 2nd
The three systems of black water were setup on different times and the results cannot be compared effectively. So, the systems are set again at same time. For this, the black water in previous systems is mixed and used.
Determined COD
29/04/2022 – 31/05/2022
Without bubbler (Water hyacinth) | Without bubbler (Indian shot) | With bubbler (Water hyacinth) | With bubbler (Indian shot) | Flood and drain (Water hyacinth) | Flood and drain (Indian shot) | |
Initial COD (mg/lit) 30/04/2022 | 918 | 918 | 918 | 918 | 918 | 918 |
03/05/2022 | 714 | 714 | 714 | 510 | 510 | 306 |
06/05/2022 | 612 | 510 | 510 | 408 | 306 | 204 |
For 3rd trial, black water is collected again and distributed in system on 10/05/2022. The COD of this water is 2244 mg/lit.
Without bubbler (Water hyacinth) | Without bubbler (Canna Indica) | With bubbler (Water hyacinth) | With bubbler (Canna Indica) | Flood and drain (Water hyacinth) | Flood and drain (Canna Indica) | |
Initial COD (mg/lit) 11/05/2022 | 2244 | 2244 | 2244 | 2244 | 2244 | 2244 |
14/05/2022 | 2193 | 2193 | 2193 | 2142 | 2040 | 1836 |
17/05/2022 | 2040 | 1836 | 1785 | 1428 | 1530 | 1224 |
20/05/2022 | 1938 | 1632 | 1428 | 1122 | 1122 | 918 |
23/05/2022 | 1836 | 1326 | 1224 | 918 | 816 | 408 |
26/05/2022 | 1785 | 1122 | 918 | 612 | 510 | 204 |
From the observations of trial taken, it is seen that the sustainability of water hyacinth is less in black water. It starts to wilt in 4-5 days. So in 4th trial, it is decided to dilute the black water with tap water. For dilution following calculation is done:
Without bubbler (Water hyacinth) | Without bubbler (Canna Indica) | With bubbler (Water hyacinth) | With bubbler (Canna Indica) | Flood and drain (Water hyacinth) | Flood and drain (Water hyacinth) | |
28/05/2022 | 2244 | 2244 | 2244 | 2244 | 2244 | 2244 |
31/05/2022 | 1785 | 1122 | 918 | 612 | 510 | 204 |
Result
Without bubbler (Water Hyacinth) | Without bubbler (Canna Indica) | With bubbler (Water Hyacinth) | With bubbler (Canna Indica) | Flood and drain (Water Hyacinth) | Flood and drain (Canna Indica) | |
% losses in COD IN 15 days | 20% | 50% | 59% | 72% | 77% | 90% |
Conclusion
- In black water, water hyacinth was sustaining in starting period but after 4-5 days it started to wilt which can be seen from the figure 18. The growth of Canna Indica is better than water hyacinth. The roots were growing
- COD is decreased in every system. But maximum decrease in COD is found in flood and drain system compared to others.
- The system with Canna Indica plants shows better results. The COD reduces more in system with Canna Indica.